Products / Liquid Cooling / ROCAS 418 AC
Representative product render. Final appearance may vary.
Liquid Cooling / C&I
ROCAS 418 AC
418 kWh | Energy Storage System
Modular liquid-cooled storage with battery protection, leakage detection, real-time monitoring and fault recording. The linked PDF describes a DC cabinet with an external conversion system; it is documented separately.
418 kWh215 kW
PRODUCT DATA
Technical specifications
AC CONFIGURATION / WEB
| Rated output | 215 kW |
|---|---|
| Voltage / wiring | 400 V (-15% to +10%); 3P+PE |
| Grid frequency | 50/60 Hz ±2.5 Hz |
| Maximum PCS efficiency | 98% |
BATTERY
| Cell chemistry / rating | LFP; 3.2 V / 314 Ah |
|---|---|
| Configuration | 1P416S |
| System energy | 417.996 kWh at 25°C / 0.5P |
| DC range | 1,123.2-1,497.6 V |
| Cycle life | 8,000 cycles (0.5P, 25 ±2°C, 70% SOH) |
SYSTEM / WEB
| Charge/discharge rate | ≤0.5P |
|---|---|
| Display | Touch screen, optional |
| Dimensions W × D × H | 1,300 ×1,350 ×2,500 mm |
| Weight | 3,700 kg |
| Enclosure / pack | IP54 / IP67 |
| System efficiency | ≥88% |
| Ambient temperature | -30 to +55°C |
| Cooling / fire suppression | Liquid cooling / aerosol |
| Listed standards* | GB/T 34120; GB/T 36276; IEC 62477; IEC 62619; IEC 61000 |
| Transport reference* | UN 38.3 (web badge) |
Technical notes & source documentation
Do not merge the AC with the linked DC-cabinet PDF. The latter lists 3,600 kg, ≥94% efficiency and -20 to +55°C; see the technical portfolio.
Reference model: SE418L-215K (web); SE418L (linked PDF). Listed standards are source references; model-specific conformity documentation is available for project review.
Manufacturer source page ↗Complete Liquid Cooling portfolio ↓